Citation: MOURA, Ailson Pereira de; LOPES, Joao Abel Peças; MOURA, Adriano Aron Freitas de. Sequence networks to the calculation of two-simultaneous faults at the same location. International Journal of Electrical Power & Energy Systems, v. 69, p. 414-420, jul. 2015.
Abstract: The system of symmetrical components (012-system) can be used to simulate symmetrical and asymmetrical operation of power systems. However, the classical literature of Power Systems Analysis does not present one equivalent circuit in 012-system to two-simultaneous faults where there are a single-line-to-ground fault and a bolted line-to-line fault. This paper presents the equations and the new equivalent circuit mentioned. In addition, we present a comparison of results between the proposed approach and the output of the commercial software ANAFAS, which validates the methodology. We find evidence that the new equivalent circuit developed can substitute the equivalent circuits used to calculate a single line-to-ground fault and a bolted line-to-line fault.
URI: http://www.repositorio.ufc.br/handle/riufc/64469
ISSN: 0142-0615
Access Rights: Acesso Aberto
Appears in Collections:DEEL - Artigos publicados em revista científica

Files in This Item:
File Description SizeFormat 
2015_art_apdemoura1.pdf2,56 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.