Título: Smart protection system for microgrids with grid-connected and islanded capabilities based on an adaptive algorithm
Autor(es): Sampaio, Felipe Carvalho
Tofoli, Fernando Lessa
Melo, Lucas Silveira
Barroso, Giovanni Cordeiro
Sampaio, Raimundo Furtado
Leão, Ruth Pastôra Saraiva
Palavras-chave: Adaptive protection systems;Directional overcurrent relays;Distributed generation;Metaheuristics;Microgrids;Sistemas de proteção adaptáveis;Relés de sobrecorrente direcionais;Geração distribuída;Metaheurísticas;Microrredes
Data do documento: 2023
Instituição/Editor/Publicador: Energies
Citação: SAMPAIO, Felipe Carvalho; TOFOLI, Fernando Lessa; MELO, Lucas Silveira; BARROSO, Giovanni Cordeiro; SAMPAIO, Raimundo Furtado; LEÃO, Ruth Pastôra Saraiva. Smart protection system for microgrids with grid-connected and islanded capabilities based on an adaptive algorithm. Energies, [S.L.], v. 16, p. 2273, 2023.
Abstract: This work proposes a smart protection system for microgrids, which relies on an adaptive metaheuristic for the automatic calculation of optimal settings for directional overcurrent relays (DOCRs). The adaptive fuzzy directional bat algorithm (AFDBA) associated with a fuzzy inference system (FIS) is used for this purpose. A prominent advantage of this solution is that there is no need for an initial tuning of the parameters associated with the algorithm, unlike many traditional approaches reported in the literature. Such a metaheuristic is used in the conception of an adaptive protection system (APS) in the context of a microgrid while taking into account the connection status of distributed generation (DG) units under distinct scenarios. A performance comparison with a protection system with fixed optimal settings (PSFOS) is also presented. The results demonstrate that the proposed APS outperforms the PSFOS while providing faster response, higher reliability and less susceptibility to miscoordination. In other words, it presents a shorter trip time when compared with he PSFOS, with a reduction of 6.83% and 26.58% when considering the DG penetration and the islanded microgrid, respectively
URI: http://www.repositorio.ufc.br/handle/riufc/73297
ISSN: 1996-1073
Tipo de Acesso: Acesso Aberto
Aparece nas coleções:DEEL - Artigos publicados em revista científica

Arquivos associados a este item:
Arquivo Descrição TamanhoFormato 
2023_art_fcsampaio.pdf1,3 MBAdobe PDFVisualizar/Abrir